Fire-rated timber door specification must cover the door leaf, frame, intumescent seals, ironmongery, and gaps as a single tested assembly. Specifying just "FD30 door" without the frame and ironmongery is the most common compliance failure. This template covers the complete tested assembly per EN 1634-1.
Free Download
NBS-format clause, common errors checklist, and standards reference. Editable PDF format ready for your tender documents.
We respect your privacy. No marketing email — only project-related technical updates if you opt in later.
Specification Checklist
FD30, FD60, FD90, FD120 (minutes). Per EN 1634-1 or BS 476-22 test certificate.
Door, frame, seals, glazing, and ironmongery must be a single tested combination — no mixing.
Solid timber, particleboard core, or glazed. Veneer or paint finish to match architecture.
Solid hardwood (typically Oak or Sapele) or hardwood-clad softwood. Frame is part of the test.
Combined intumescent + smoke seal, fitted in frame groove (or door edge).
Pyran or Pyroguard glass, with intumescent glazing strip per door manufacturer.
CE-marked fire door hinges, 3 minimum per leaf, with intumescent pads if required.
Self-closing device per BS EN 1154, controlled closing.
3mm head and side, 8mm threshold maximum (or as per test certificate).
BWF Fire Door Alliance Q-Mark or equivalent. Each door uniquely identified.
Example Clause (NBS Format)
FIRE-RATED TIMBER DOORS Fire rating: FD30S (30 minutes integrity, with smoke seal) per BS 476-22 or EN 1634-1 Door leaf: - Construction: Engineered solid core, paint-grade finish - Thickness: 44mm - Manufacturer: BWF Fire Door Alliance Q-Mark certified - Tested assembly: Complete combination (leaf + frame + ironmongery) on single test certificate Frame: - Material: European Oak hardwood, kiln dried 12% MC - Section: 38×95mm rebated, with intumescent groove - Architraves: Square edge oak, 19×69mm - Fixing: 4 fixings per jamb, into masonry or timber stud Intumescent seals: - Type: 15×4mm intumescent + smoke seal combined - Location: Frame groove, all three sides Ironmongery: - Hinges: CE-marked Grade 14 fire door hinges, 3 per leaf - Latch / lock: Fire-tested, with intumescent strike plate - Closer: BS EN 1154 controlled closing device, Power Size 3 minimum - Signage: "FIRE DOOR KEEP CLOSED" label, both sides Glazing (where specified): - Glass: Pyrobel 7mm or equivalent, fire-tested for FD30 - Beading: Hardwood with intumescent strip behind glazing Gaps: - Head: 3mm maximum - Sides: 3mm maximum - Threshold: 8mm maximum (or per test certificate) Identification: Each door uniquely numbered with manufacturer's plug or label, traceable to certificate.
Copy and paste this clause into your tender. Adjust dimensions, grades, and project-specific requirements.
Common Errors
Mixing door leaf from one supplier with frame from another
Correction: Fire doors are tested as complete assemblies. Always specify "tested combination" from a single Q-Mark certified supplier.
No intumescent seals
Correction: Mandatory for FD30+. Without seals, the assembly fails at first sign of smoke.
Generic "FD30 hinges"
Correction: Specify CE-marked Grade 14 fire-tested hinges. Standard hinges may not be tested for fire performance.
Gaps wider than test certificate
Correction: Each test certificate states maximum gaps. Site adjustment must stay within these limits.
No identification marking
Correction: Each fire door must be uniquely identified for inspection and replacement traceability.
Reference Standards
Frequently Asked
FD30 = 30 minutes integrity (resists fire passage for 30 minutes). FD30S = FD30 + smoke seal (also resists smoke transmission). Building Regs typically require FD30S for flat entrance doors.
Yes, with fire-tested glass (Pyran, Pyrobel) and intumescent glazing strips. Glazing area is limited per the test certificate (typically max 1m² for FD30).
Annual inspection minimum. Six-monthly for high-traffic or critical locations. Inspection records must be kept and signed off by competent person per Regulatory Reform (Fire Safety) Order 2005.